SPR-JK200Y Accident Fan Monitor
Contact Info
- Add:陕西省西安市翠华路60号, Zip:
- Contact: 刘品宜
- Tel:13572979371
- Email:243616989@qq.com
Other Products
Emergency Fan Monitor
The SPR-JK200Y Emergency Fan Monitor is used to monitor the operational status of emergency fans and their related interconnected equipment in data centers.
Definition The Emergency Fan Monitor is used in exhaust gas emergency fan monitoring systems. It allows remote control of emergency fans and their interconnected equipment for daily ventilation and exhaust gas emission, and displays the working status of emergency fans and controlled equipment in real time.
Application Areas Data center rooms, battery rooms, equipment rooms, and other critical equipment locations equipped with fire suppression systems.
Working Principle The exhaust gas emergency fan monitoring system is designed to reliably monitor emergency fans and their related interconnected equipment in data centers. After a gas fire suppression system extinguishes a fire, it quickly and effectively removes high concentrations of harmful gases from the protected area, significantly reducing the waiting time for resuming normal communication operations and minimizing accident losses. When the hydrogen concentration in a battery room reaches a set value, the combustible gas detection system sends a signal, and the exhaust gas emergency fan monitoring system activates the emergency ventilation system to reduce hydrogen concentration. It also serves as a daily exhaust system under normal conditions. This system effectively addresses the quantitative management of emergency ventilation systems in various environments, improves the interconnected logic of monitoring, management, and control during operation, and ensures the normal functionality and usage of the emergency ventilation system. The exhaust gas emergency fan monitoring system mainly consists of an emergency fan monitor, interconnected fan controller, manual control device, interconnected control device, and specialized system monitoring software.
Installation Location The Emergency Fan Monitor is installed in the fire control room using a wall-mounted installation method.
For system configuration, product parameters, and pricing, please call our company.
Contact: Manager Liu
Phone: 13572979371 (same number for WeChat — 135 729 79371)
We are dedicated to providing comprehensive solutions and product services!!!
| Industry Category | Measurement-Analysis-Instruments |
|---|---|
| Product Category | |
| Brand: | |
| Spec: | SPR-JK200Y |
| Stock: | |
| Origin: | China / Shaanxi / Xianshi |